- Device can be registered. Web-based management indicates that the device cannot connect.
- Device can be registered, but the Web Based Management does not show an active connection to Proficloud.io.
- Device cannot be registered.
- Device is online in the Web Based Management, but offline in the Device Management Service.
- Variables are available in PLCnext Engineer, but no metrics are visible in the device entry.
- Firmware 2025 results in missing DNS resolution (device is no longer online after the firmware update). ME
- I receive the message “Connection attempt failed. MQTT error” in the Web Based Management of my PLCnext controller.
Device can be registered. Web-based management indicates that the device cannot connect.
Affected devices
Affects all devices on Proficloud.io
Problems
Device has been registered, but appears offline in the Device Management Service.
Possible cause
Missing or limited internet connection.
Inspection by the user
- Is the corporate firewall blocking ports or DNS?
- Are the following domains reachable?
`proficloud.io` and `proficloud-production.io`
- Is access to the PLCnext Store possible from the device?
Options for action
- Check network permissions
- Ensure ports 443 (HTTPS) and 8883 (MQTT over TLS)
Responsibility
- User configuration required
Device can be registered, but the Web Based Management does not show an active connection to Proficloud.io.
Affected devices
- AXC F 2152
- AXC F 3152
- AXC F 1152
- EPC 1502
- EPC 1522
Problems
The device was registered but appears offline in the Device Management Service.
Possible cause
Missing or incorrect Proficloud configuration on the device.
Inspection by the user
The user must check in the Web Based Management of the device whether the Proficloud services are all correctly enabled.
Under Configuration → Proficloud Services, the following options must be checked in order to use Proficloud.io or the Device Management Service:
- Enable Connection
- Device Management
- Time Series Data
The user can verify in the certificates whether the configuration on the device is faulty.
Security → Certificate Authentication → Trust Stores
Entry: “Proficloud” with five certificates
Security → Certificate Authentication → Identity Stores
Entry: “Proficloud” with three elements
Options for action
- Check the configuration
- If certificates are missing, update the firmware locally. The update ensures that the certificates are properly loaded.
Responsibility
User checks and corrects the configuration.
Note
Some firmware versions do not reliably create trust/identity stores.
Device cannot be registered.
Affected devices
Affects all devices on Proficloud.io
Problems
Registration fails in the Device Management Service.
Possible cause
UUID already registered in another organization.
Inspection by the user
Determine the organization in which the device already exists.
Options for action
Contact colleagues and have the device deleted there.
Responsibility
Support can assist. Please get in touch via inbox@phoenixcontact-sb.io.
Device is online in the Web Based Management, but offline in the Device Management Service.
Affected devices
- AXC F 2152
- AXC F 3152
- AXC F 1152
- EPC 1502
- EPC 1522
Problems
Controller shows online in Web Based Management but offline in the Device Management Service.
Possible cause
Status inconsistency between the device and the DMS.
Inspection by the user
Check the sending of data in the Time Series Data Service.
Options for action
The display is incorrect, but the function is intact.
Responsibility
Support kann unterstützen, bitte mit inbox@phoenixcontact-sb.io in Kontakt treten
Variables are available in PLCnext Engineer, but no metrics are visible in the device entry.
Affected devices
- AXC F 2152
- AXC F 3152
- AXC F 1152
- EPC 1502
- EPC 1522
Problems
Device sends data, but variables do not appear in the metric assignment.
Possible cause
Variables incorrectly defined or not marked as IoT/outport.
Inspection by the user
In PLCnext Engineer:
- Set the variable to Outport
- Enable the “IoT” column
Options for action
Adjust variables and redeploy.
Responsibility
User
Note
- Structures are not transferred
- Visibility only after data transmission in the Device Management Service
Firmware 2025 results in missing DNS resolution (device is no longer online after the firmware update). ME
Affected devices
- AXC F 2152
- AXC F 3152
- AXC F 1152
- EPC 1502
- EPC 1522
Problems
After updating from firmware 2024 to firmware 2025, the device loses internet access.
Possible cause
- DNS resolution not functional
- Occurs when the device is updated from firmware versions 2024 to 2025
Inspection by the user
Ping the controller and check the internet connection in the Web Based Management Service.
Options for action
Factory reset as a possible solution (results in loss of application, IP address data, users)
I receive the message “Connection attempt failed. MQTT error” in the Web Based Management of my PLCnext controller.
Affected devices
- AXC F 2152
- AXC F 3152
- AXC F 1152
- EPC 1502
- EPC 1522
Problems
This message occurs when a device fails to establish a successful MQTT connection with Proficloud.io. The connection is made using a unique client certificate and the corresponding private key. Both are used to authenticate the device to P
Possible cause
If the device has been reset to factory settings, the certificate and private key are deleted. The device can no longer register until a new private key has been provided. For security reasons, the renewed provisioning of the private key must be manually enabled on Proficloud.io.
Inspection by the user
- Select the device in the Device Management Service and click the three-dot menu.
- Choose “Reset Token”.
- The rollout of the certificate and private key is now enabled for ten minutes. During this time window, the device must initiate the connection again.